Industrial Style Gas Mass Flow Meters for high flow rates

Bronkhorst® model F-107DI Mass Flow Meters (MFMs) are suited for precise measurement of flow ranges between 3,6…180 m3n/h and 36…1800 m3n/h at operating pressures up to 40 bar. The MFM consists of a thermal mass flow sensor and a microprocessor based pc-board with signal and fieldbus conversion and a PID controller for optional mass flow control by means of a separately mounted control valve. The IN-FLOW model is of rugged design (IP65) for use in industrial environments or even Zone 2 hazardous areas, with optional ATEX Cat. 3 or FM Class I, Div. 2 approval.

IN-FLOW series are equipped with a digital pc-board, offering high accuracy, excellent temperature stability and fast response. The main digital pc-board contains all of the general functions needed for measurement and control. In addition to the standard RS232 output the instruments also offer analog I/O. As an option, an on-board interface can be mounted to provide CANopen®, DeviceNet™, EtherCAT®, PROFIBUS DP, PROFINET, Modbus RTU, ASCII or TCP/IP, EtherNet/IP, POWERLINK or FLOW-BUS protocols.


Technical specifications

Measurement / control system
Flow range (intermediate ranges available)min. 3,6…180 m3n/h
max. 36…1800 m3n/h
(based on N2)
Accuracy (incl. linearity) (based on actual calibration)± 1 % FS
Repeatability< 0,2 % RD
Turndown ratio1:50
Multi fluid capabilityStorage of max. 8 calibration curves
Response time (sensor)typical: 0,5 sec.
Operating temperature-10 … +70 °C
for ATEX cat. 3 and FM Class 1 Div 2 : 0…50°C
Temperature sensitivityzero: < 0,05% FS/°C; span: < 0,05% Rd/°C
Pressure sensitivity0,1% Rd/bar typical N2; 0,01% Rd/bar typical H2
Leak integrity, outboardtested < 2 x 10-9 mbar l/s He
Attitude sensitivitymax. error at 90° off horizontal 0,2% FS at 1 bar, typical N2
Warm-up time30 min. for optimum accuracy
2 min for accuracy ± 2% FS
Mechanical parts
Material (wetted parts)stainless steel 316L or comparable
Pressure rating (PN)up to 40 bar abs
Process connectionsFlanged type, according to DIN DN100 or ANSI 4”
Sealsstandard: FKM/Viton®;
options: EPDM, FFKM/Kalrez®
Weight25,4 kg
Ingress protectionIP65
Electrical properties
Power supply+15 … 24 Vdc
Max. power consumption
Supply
15 V
24 V
at voltage I/O
95 mA
65 mA
at current I/O
125 mA
85 mA
extra for fieldbus
<75 mA
<50 mA
Analog output0…5 (10) Vdc or 0 (4)…20 mA (sourcing output)
Digital communicationstandard: RS232;
options: CANopen®, DeviceNet™, EtherCAT®, PROFIBUS DP, PROFINET, Modbus RTU, ASCII or TCP/IP, EtherNet/IP, POWERLINK or FLOW-BUS
Electrical connection
Analog/RS2328 DIN (male);
PROFIBUS DPbus: 5-pin M12 (female);
power: 8 DIN (male);
CANopen® / DeviceNet™5-pin M12 (male);
FLOW-BUS/Modbus-RTU/ASCII5-pin M12 (male);
Modbus TCP / EtherNet/IP / POWERLINKbus: 2 x 5-pin M12 (female) (in/out);
power: 8 DIN (male);
EtherCAT®/ PROFINETbus: 2 x 5-pin M12 (female) (in/out);
power: 8 DIN (male)
IEC 61010-1IEC-61010-1:2010 including national deviations for UL (61010-1:2012) and CSA (C22.2 No. 61010-1-12)
Control valve options
External actuator options to be connected to the controller
Certification for hazardous areas
Approvals / certificates

Technical specifications subject to change without notice.

For dimensional drawings and hook-up diagrams please visit the product page on our website

Downloads

Brochures
IN-FLOW brochure
Manuals
General manual digital instruments
Operating instructions digital instruments
Hook-up diagrams
Analog IO - RS232
DeviceNet
FLOW-BUS
Modbus RTU/ASCII
PROFIBUS DP
Industrial Ethernet (EtherCAT, EtherNet/IP, Modbus-TCP, POWERLINK, PROFINET)
CANopen
Optional Bus and IO Configurations
Dimensional drawing
Dimensional Drawings F-107I
Certificates
ATEX: KEMA 10ATEX0111X
KCs certificate IN-FLOW MFM (Korean)
FM approval Class I, Div. 2 (US), FM17US0363X
FM approval Class I, Div. 2 (CA), FM17CA0173X